| KPM10Multifunction meter-Technical parameters | 
		
			| Working power source | Operating Voltage | AC85~265V/DC80~300V | 
		
			| Rated power | <3VA | 
		
			| Input voltage | Rated voltage | 57.7/100V, 220/380V, 380/660A(needs customization) | 
		
			| Sill value | 5V | 
		
			| Overload capacity | 1.2 times rated voltage allowed, continuous work; 2 times the rated voltage allowed 1second | 
		
			| Power consumption | <0.5VA/phase(rated) | 
		
			| Measurement range | 5~260VAC, | 
		
			| Frequency range | 45~65Hz | 
		
			| 輸入電流/Input current | Rated current | Default 5A,Input range 1-6A;Optional 1A,Input range 1-1.2A | 
		
			| Sill value | 5A Configuration,5mA;1A Configuration,0.8mA | 
		
			| Overload capacity | 1.2 times rated current allowed, continuous work; 20 times the rated current allowed 1 second | 
		
			| Power consumption | <0.75VA/phase(Rated current 5A);<0.25VA/phase(Rated current 1A) | 
		
			| Frequency range | 45~65Hz | 
		
			| Input/Output | Switch value input | 2-way passive main line contact DI input, internal supply DC24V power source | 
		
			| Relay output | 2-way DO output,Contact capacity 250VAC/5A,30VDC/5A | 
		
			| Power quality monitor | Harmonic measurement | Voltage/current2~21th harmonic distortion rate、total harmonic distortion rate. | 
		
			| Harmonic distortion rate | Phase voltage, line voltage | 
		
			| Imbalance rate | Voltage. current | 
		
			| Measurement accuracy | Voltage | ±0.2%(0.01V) | 
		
			| Current | ±0.2%(0.01A) | 
		
			| Active power | ±0.5%(0.1W) | 
		
			| Reactive power | ±2.0%(0.1kvar) | 
		
			| Active energy | ±0.5%(0.1kWh) | 
		
			| Reactive energy | ±2.0%(0.1kvarh) | 
		
			| Power factor | ±0.5%(0.001) | 
		
			| Frequency | ±0.02Hz(0.01Hz) | 
		
			| Temperature | ±1℃(1℃) | 
		
			| Communication | Communication interface | RS485,Photoelectric isolation interface | 
		
			| Communication protocol | Modbus-RTU,1200~38400bps | 
		
			| Electrical insulation | Power frequency withstand voltage | AC2kV/min~1mA Input-output-power source (GB/T 13729) | 
		
			| Insulation resistance | >50MΩ                            (GB/T 13729) | 
		
			| Impact voltage | 5kV(Peak),1.2/50us    (GB/T 13729) | 
		
			| Working environment | Operating temperature | -25℃ ~ +70℃ | 
		
			| Relative humidity | 5%~95% No condensation | 
		
			| Storage temperature | -30℃ ~ +75℃ | 
		
			| Altitude | No more than 4000m | 
		
			| Electromagnetic Compatibility | Surge (impact) immunity | GB/T 17626.5-2008,Level4 | 
		
			| Electrical fast burst immunity | GB/T 17626.4-2008,Level4 | 
		
			| Electrostatic discharge immunity | GB/T 17626.2-2006,Level4 | 
		
			| Power frequency magnetic field immunity | GB/T 17626.8-2006,Level4 |